    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay|Process Controllers
    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay|Process Controllers
    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay|Process Controllers
    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay|Process Controllers
    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay|Process Controllers
    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay|Process Controllers

    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay

    900CPR-1-BL-U-CE

    900CPR-1-BL-U-CE - Digital 1Ø Current Protection Relay
    - Backlit Liquid Crystal Display


    Features

    •  1Ø - 2 Wire Input

    • Monitors Under current and Over current

    • True RMS measurement

    • Power ON delay, Trip time delay and Recovery time delay

    • Adjustable switching hysteresis

    • Two alarm relay with NC or NO operation selectable

    • LCD with backlight

    • DIN Rail Mount

    • Size: 35mm (Width)

     DATA Sheet Link

    < Product photo may vary depending on part number selection.

     

    Analog / Digital Protection Relays

    Protection
    Altech is pleased to offer a variety of protection relays covering:

    • Phase Monitoring

    • Voltage Monitoring

    • Current Monitoring

    • Frequency Monitoring

    Current Leakage / Ground Fault Monitoring Protection relays help to maintain systems and ensure that proper action is taken when a fault is detected. Such functions help to preserve productivity and operational effectiveness of integral components. 

    Process Controllers - Supply Voltage
    85-270V AC/DC
    Process Controllers - LED Indication
    LED 1: Relay 1, LED 2: Relay 2
    Process Contollers - Input Voltage
    85-270 V AC/DC
    Process Controllers - Input Measurement
    Current Transformer-Under Current / Over Current
    Process Controllers - Trip Setting
    Under Voltage: 85-500 V AC [L-L] (3Ø-3 wire) 50-288 V AC [L-N] (3Ø-4 wire), Over Voltage: 85-500 V AC [L-L] (3Ø-3 wire), 50-288 V AC [L-N](3Ø-4 wire), Under Frequency: 45-65Hz,* See Data Sheet for more information
    Process Controllers - Main Output
    SPDT -2 C/O - NO: 5A, 250 V AC and NC:3A, 250 V AC
    Process Controllers - Trip Time Settings
    Power ON Delay: 0.5-99.9 sec / Trip Time Delay: 0-99.9 sec / Recovery Time Delay: 0-99.9 sec / Response Time: greater than 200ms
    Process Controllers - Hysteresis
    Current: 0.1-99.9A
    Process Controllers - Reset
    Auto/Manual (Selectable)
    Process Controllers - Power Consumption
    4VA max
    Process Controllers - Operating Temperature
    0 to 50°C (32 to 122°F)
    Process Controllers - Storage Temperature
    -20 to 70°C (-4 to 158°F)
    Process Controllers - Humidity (Non-Condensing)
    95% Relative Humidity
    Process Controllers - Weight
    150 grams (.33 lbs)
    Process Controllers - Display Type
    Liquid Crystal Display
    Process Controllers - Digits
    1 row of 3 digits
    Process Controllers - Latching
    Selectable
    Process Controllers - Electrical Connection
    1Ø-2 wire
    Process Controllers - Current
    +/- 1% of setting, +/- 2 digits
    Process Controllers - Protection Level
    IP50 (for faceplate), IP30 (for housing), IP20 (for terminals)
    Process Controllers - Alarm Indications
    Trip
    Process Controllers - CT Setting
    CT: Primary 1A/5A - 999A / CT secondary 1A/5A (Selectable)
    Process Controllers - Time Setting
    +/- 5% of setting, +/- 100ms